FuelVu - Model Selection & Options

FuelVu

Standard Designs: Wall-Mount (2, 4 & 7 GPM) & Large Capacity Free-Standing Series

MODEL GPM1 GPH1 TANK SIZE2
GALLONS
25% CYCLE
TIME – HRS
33% CYCLE
TIME – HRS
HP1 VOLTAGE PIPE SIZE
IN. NPT
FVU-2
2
120
up to 3,600
0.5-7.5
0.7-9.9
0.7-9.9
115/230-1-60V, 6.6/3.3A
230/460-3-60V, 1.6/0.8A
1.0
FVU-4
4
240
4,000-8,000
4.2-8.3
5.5-11
0.33
115/230-1-60V, 6.6/3.3A
230/460-3-60V, 1.6/0.8A
1.0
FVU-7
7
420
8,200-13,440
4.9-8
6.4-10.5
0.5
115/230-1-60V, 8.8/4.4A
230/460-3-60V, 2.4/1.2A
1.0
FVU-10
10
600
12,000–20,000
5-8.3
6.6-11.0
0.75
115/230-1-60V, 11.0/5.5A
230/460-3-60V, 2.8/1.4A
1.0
FVU-15
15
900
16,000-22,000
4.4-6.1
5.9-8.1
1.0
115/230-1-60V, 13.4/6.7A
230/460-3-60V, 3.6/1.8A
1.5
FVU-20
20
1200
20,000-30,000
4.2-6.25
5.5-8.3
1.5
115/230-1-60V, 18.0/9.0A
230/460-3-60V, 4.8/2.4A
2.0
FVU-30
30
1800
28,000-40,000
3.9-5.6
5.2-7.4
2.0
230-1-60V, 10.5A
230/460-3-60V, 5.8-2.9A
2.0
FVU-40
40
2400
38,000-55,000
4.0-5.7
5.3-7.6
3.0
230-1-60V, 17.5A
230/460-3-60V, 8.4/4.2A
2.0
FVU-50
50
3000
50,000-75,000
4.2-6.25
5.6-8.3
3.0
230-1-60V, 17.5A
230/460-3-60V, 8.4/4.2A
2.0

1GPM/HP @ 32SSU, 50PS

2Single Tank Capacity Only

Note: We are experts at building products that meet our customer’s exact requirements. Contact us if your job specifications require additional options or considerations.

FuelVu Stand Alone Systems are designed for much larger tank capacities. Even under high pressure gpm, precision fuel analysis remains with repeatability of +/-2 ISO count.

FuelVu Automated Fuel Polishing and Integrated Fuel Analysis

Standard System Includes:

  • I-Vu Fuel Laser Analyzer
  • Indoor wall-mountable
  • 1 through 2-inch NPT or flanged field connections
  • On-board, integrated digital controller, UL508A
  • MODBUS or Ethernet network compatible
  • Inlet, outlet ball-type shutoff valves
  • Check valve
  • Pressure/vacuum gauges
  • Pressure transducers, water detector
  • Circulation pump, GPM and HP as per Model Section

Options:

  • FVU-10: Stainless Steel Belly Tank Leak sensor
  • FVU-20: Outdoor NEMA Steel Enclosure
  • FVU-30: Outdoor enclosure with internal cabinet heater and thermostat
  • FVU-40: FBO indoor cold environment coalescent heater
  • FVU-50: 1–Micron final filter element
  • FVU-60: Tank level sensor for display and alarms
  • FVU-70: Magnetic in-line fuel conditioner installed
  • FVU-80: BacNet communication port
  • FVU-90: Low or High Level Alarm/Overfill sensor

For replacement filters and water coalescing elements please contact us.

(Larger and Custom Capacities Available, please contact us for more information.)

Standard Filtration Elements Included:

  • Strainer @ 40 mesh
  • 5 Micron Particulate Filter
  • Water Coalescer / Water Separator to 15 ppm
  • Replacement filters readily available, please contact FuelVu

Replacement Filters
Filters are used to protect the OEM supplied fuel system.

Coalescer/Separator
Coalescer/separator filters are a two stage element that removes water and contaminants from diesel fuel streams and are the most popular filters

Particulate Filters
Particulate filters remove contaminants down to one micron. Particulate filters can also be used upstream, before a water separator filter, to extend filter life.

Water Absorber
Water absorber absorbs water and filters out contaminants from diesel fuel.

Part#
FBO 60338

FBO Micron Rating Coalescer/Separator


FBO-14
(6 x 14 Filter)

(6 x 14 FilterFBO-14
(6 x 14 Filter)

1
FBO 60336
5
FBO 60337
10
FBO 60356
25
FBO 60338